08-07
Model Name
Indoor unit
Outdoor unit
V
Hz
Cooling Heating
Current A
Input Kw
Max Operating Current A
Starting Current A
Main Fuse (Circuit breaker)
Current
A
Power Cable
mm
2
*2)Limited wiring length m
Input Kw
Full Load Amp. A
Input Kw
Full Load Amp. A
AR*45LUAN
AO*45LJBYL
Power Supply
Rated Value
Mode
*1) Wiring Spec
Outdoor Fan Motor
Indoor Fan Motor
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2 Limited Wiring length : This is the wiring length in case voltage descent is less than 2%
When the wiring length becomes long, please select the wiring of a more
larger diameter.
19.5
17.3
4.45
3.95
22.6
22.5
50
15
230
0.34 x 2
6.0
30
27
0.067 × 2
0.150
0.670
Indoor unit
Outdoor unit
Voltage V
Frequency Hz
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
Current A 23.6 20.6 18.9 16.7 23.5 19.8 18.1 16.0
Input kW 5.36 4.70 4.30 3.80 5.57 4.70 4.30 3.80
Max Operating Current A 25.9 25.9 22.6 22.5 25.9 25.9 22.5 22.5
Starting Current A 15 15 15 15 15 15 15 15
Main Fuse (Circuit
breaker) Current
A
Power Cable
mm
2
*2)Limited wiring length m
Input kW
Full Load Amp. A
Input kW
Full Load Amp. A
13.3-5.3
ART45LUAK
AOT45LJAYL
3.5
30
230 240
0.34 x 2
0.7
0.067 x 2
55-22
Mode
AR 54LUAK AR 45LUAK ART54LUAK
AO 54LJAYL AO 45LJAYL AOT54LJAYL
50