1-23. OFF DEFROST OPEARTION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly, the outdoor unit will allow the heat exchanger to defrost, and then stop.
In heating operation, the outdoor heat exchanger temperature is less than -4°C,
compressor continuous operation more than 10 minutes, and
compressor operation
integrating time lasts for more than 30 minutes.
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature :
Below -4°C
Compressor continuous operation :
Over 10 minutes
Compressor integrating operation :
Over 30 minutes
Defrost start
Defrost Indicater:
[Operation lamp]
6 sec ON / 2 sec OFF
Outdoor heat exchanger temperature :
Over +13°C
or
Compressor ON time : Maximum 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +13°C
or Compressor operation time has passed 15 minutes.
01-22
Outdoor fan motor ON
( - 6°C< OT < 1°C )
OT :Outdoor Temperture
= =

Other manuals for Fujitsu AO G24LBCB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G24LBCB Series and is the answer not in the manual?

Fujitsu AO G24LBCB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G24LBCB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals