1-2. HEATING OPERATION
1-2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 3 degC than a set temperature,
the compressor operation frequency will attain to maximum frequency.
* If the room temperature is higher 2.5 degC than a set temperature, the compressor
will be stopped.
* When the room temperature is
between +2.5 degC to -3 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
01-02
minimum
frequency
maximum
frequency
10rps 110rps
Operating
frequency
29 rps
1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Fig 2.
Room
temperature
Room
temperature
Compressor ON
Ts-0.5 degC
Ts-1.5 degC
Compressor OFF
( Table
3
: Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
Ts : Setting temperature