6. HEATING OPERATION (Auto : Heating)
01-06
3. COOLING OPERATION (Auto : Cooling)
( Fig.5 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > - 1.5 degC
=
- 2.5 degC > TR-Ts
- 1.5 degC > TR-Ts > - 2.5 degC
=
TR-Ts > 2 degC
=
1 degC > TR-Ts
2 degC > TR-Ts > 1 degC
=
TR-Ts > 2.5 degC
=
1.5 degC > TR-Ts
2.5 degC > TR-Ts > 1.5 degC
=
TR-Ts > - 1 degC
=
- 2 degC > TR-Ts
- 1 degC > TR-Ts > - 2 degC
=
High mode
Med mode
Low mode
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Low mode
Med mode
High mode
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 5.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 7.
On the other hand, if switched [HIGH] [QUIET], the indoor motor will run at a constant airflow of [HEAT]
operation modes QUIET, LOW, MED, HIGH, as shown in Table 5.
4. DRY OPERATION (Auto : Dry)
Refer to Table 6. During the dry mode operation, the fan speed setting can not be changed.
Compressor
ON
OFF
Indoor fan
Dry air flow
S-Lo
OFF
( Fig.6 : Indoor Fan Control )
10 30 60 180 60 180 60 10 30
(SEC)
5. INDOOR UNIT FAN CONTROL FOR ENERGY SAVING (Cooling mode)
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.6.
It depends on the Function setting "Indoor unit fan control for energy saving."