Additional charging amount for Triple type
L1L4
L3
L2
Pre-charge length < L1 + L2 + L3 + L4
The additional charging amount will be calculated as follows.
A: Piping length (m) of liquid pipe with outside diameter of 9.52 mm (1/2 in)
B: Piping length (m) of liquid pipe with outside diameter of 6.35 mm (3/8 in)
Additional charging amount (g) = (A × 40) + (B × 20) - 1,200
NOTE:
Do not remove refrigerant, even if the additional amount calculated is negative.
Example:
Indoor unit
18,000 Btu/h
Indoor unit
18,000 Btu/h
Indoor unit
18,000 Btu/h
Outdoor unit
54,000 Btu/h
Liquid pipe (mm)
Gas pipe (mm)
6.35
12.70
L2: 5 m
Liquid pipe (mm)
Gas pipe (mm)
6.35
12.70
L3: 5 m
Liquid pipe (mm)
Gas pipe (mm)
9.52
15.88
L1: 10 m
Liquid pipe (mm)
Gas pipe (mm)
6.35
12.70
L4: 5 m
Liquid pipe diameter (mm) Piping length (m) Coefficient
9.52 10 A = 10
6.35 15 B = 15
Applying the formula,
(10 × 40) + (15 × 20) - 1,200 = -500
The calculated value is negative. Do not add or remove any refrigerant.
- 100 -
2-5. Additional charge calculation 2. Pipe design
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu AO G36KBTB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G36KBTB Series and is the answer not in the manual?

Fujitsu AO G36KBTB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G36KBTB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals