12. Safety devices
Type of
protection
Protection form
Model
AOYG36KRTA
AOYG45KRTA
AOYG54KRTA
Circuit
protection
Current fuse
(Main PCB)
250 V, 30 A × 2
250 V, 10 A × 2
250 V, 30 A × 2
250 V, 10 A × 2
Fan motor
protection
Thermal protection program
Activate
122 ±9 °C
Fan motor stop
150 ±15 °C
Fan motor stop
Reset
116
+10
-9
°C
Fan motor restart
120 ±15°C
Fan motor restart
Compressor
protection
Thermal protection program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection program
(Compressor temp.)
Activate
108 °C
Compressor stop
Reset
80 °C or less
Compressor restart
Thermal protection program
(Outdoor temp.)
Activate
-20 °C
Compressor stop
Reset
-15 °C
Compressor restart
- 81 -
12. Safety devices
OUTDOOR UNIT
AOYG36-54KRTA
OUTDOOR UNIT
AOYG36-54KRTA

Table of Contents

Other manuals for Fujitsu AO G36KBTB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G36KBTB Series and is the answer not in the manual?

Fujitsu AO G36KBTB Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G36KBTB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals