EasyManuals Logo

Fujitsu AO G36KBTB Series User Manual

Fujitsu AO G36KBTB Series
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #139 background imageLoading...
Page #139 background image
¢
Combination of external input and output
By combining the function setting of the indoor unit, you can select various combinations of func-
tions.
Combination examples of external input and output are as follows:
Mode Function setting
External input External output
Terminal CN47
0 60—00 Operation/Stop
1—8 60—01 to 60—08 (Setting prohibited)
9 60—09 Operation/Stop Error status
10 60—10 Operation/Stop Indoor unit fan operation status
11 60—11 Operation/Stop External heater output
NOTE: Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
Input signal type
Indoor unit
Input signal type is only "Edge".
Edge
- 131 -
6-1. Indoor unit 6. External input and output