Installation
Mounting of indoor unit
For mounting, refer to the installation manual provided with indoor unit.
When installing this product to existing indoor units, adjust the installation height of the indoor
units to height 260 to 265 mm as shown below.
Unit: mm
260 to 265
Metal hanging fastener
Ceiling
Indoor unit
Fresh air intake kit
Installation of Fresh air intake kit
CAUTION
Installing the Fresh air intake kit with wrong direction is a cause of water leakage.
1. Attach the Fresh air intake kit to the main body using the bolts provided as shown below.
Metal fittings
Bolt × 4
DRAIN
PIPE
DRAIN
PIPE
- 206 -
10-2. Fresh air intake kit for compact cassette type (UTZ-VXAA) 10. Optional parts installation