3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
( Table 24 : Anti-freezing protection operation / Release temperature )
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 152.6°F(67°C) or greater,
the compressor and the outdoor fan motor are stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL (Heating mode)
Outdoor temperature
Over than 50°F (10°C)*1
or 54°F (12°C)*2
Less than 50°F (10°C)*1
or 54°F (12°C)*2
*1. When the temperature drops.
*2. When the temperature rises.
39.2°F
(4°C)
44.6°F
(7°C)
55.4°F
(13°C)
Temperature Temperature
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange
temperature rises
Indoor heat exchange
temperature drops
It returns to the normal operation
Compressor is stopped
127.4°F
(53°C)
131°F
(55°C)
145.4°F
(63°C)
122°F
(50°C)
The compressor frequency is
decreased 3rps every 60seconds.
The compressor frequency is
decreased 25rps every 120seconds.
Stable zone
01-20