( Fig. 1 : Outdoor temperature zone )
1. COOLING OPERATION
Minimum
frequency
Maximum
frequency
AOU18RLB
AOU24RLB
12rps
12rps
Indoor fan mode
Me Lo Quiet
A zone
104rps
59rps 48rps 38rps
B zone 104rps 59rps 48rps 38rps
C zone 86rps 59rps 48rps 38rps
AOU18RLB
D zone 63rps 56rps 41rps 34rps
E zone 63rps 56rps 41rps 34rps
F zone
63rps 56rps 41rps 34rps
( Table 1 : Compressor frequency range )
01-01
AOU24RLB
( Table 2 : Limit of maximum speed based on outdoor temperature )
104rps
104rps
Outdoor
temp. zone
Hi
When the compressor operates for 30 minutes continuously at over the maximum frequencyⅡ,
the maximum frequency is changed from the maximum frequencyⅠto the maximum frequencyⅡ.
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 7°F(3.5°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
* When the room temperature is between +7°F(+3.5°C) to -1°F(-0.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table 1 .
However, the maximum frequency is limited in the range shown in Fig. 1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is 1°F(0.5°C) lower than a set temperature, the compressor will be
stopped.
Maximum
frequency
63rps
72rps
When the outdoor
temperature drops
97°F
(36°C)
A zone
93°F
(34°C)
90°F
(32°C)
B zone
86°F
(30°C)
70°F
(21°C)
C zone
66°F
(19°C)
D zone
E zone
F zone
50°F
(10°C)
32°F
(0°C)
54°F
(12°C)
36°F
(2°C)
When the outdoor
temperature rises