EasyManua.ls Logo

Fujitsu AOU18RLB - Page 35

Fujitsu AOU18RLB
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 8
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Intake Grille Error
Indoor unit Controller PCB
Micro switch
When the Micro switch is detected open while running the compressor.
1. Micro switch failure 2. Shorted connector/ wire 3.Controller PCB failure
Indicate or Display:
Check
Point 2 : Check Connector (CN11) / Wire
Check Point 1 : Check Limit switch
Check Point 3 : Replace Controller PCB
OKOK
Check operation of Micro switch. (any blocking by dust, etc.)
Remove Micro switch and check ON/OFF switching operation by using a meter.
>>If Micro switch is detective, replace it.
Check loose contact of CN11 /shorted wire (pinched wire).
>>Replace Micro switch if the wire is abnormal
OKOK
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
02-11
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 5 time Flash, Timer lamp: 8 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 58]

Other manuals for Fujitsu AOU18RLB

Related product manuals