Fujitsu AOU18RLB - Heat Ex.(Pipe) Thermistor Error

Fujitsu AOU18RLB
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 13
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
6.9 0.612.416.121.027.8Resistance Value (k )
Temperature (°F)
OKOK
OKOK
3.8
2.1 8.0 6.0
5.2 7.1
Resistance Value (k )
Temperature (°F)
Heat Ex.(Pipe) Thermistor Error
Outdoor unit Main PCB
Heat exchanger thermistor
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or miss-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
23°F14°F
176°F158°F140°F
86°F68°F50°F41°F32°F
122°F104°F
Indicate or Display:
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-16
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 3 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 73]