8. COMPRESSOR CONTROL
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table8.
Cooling Heating
Min Max Min Max Min Max
Dry
ASU18RLF
ASU24RLF
12rps 55rps 14rps 67rps 15rps 25rps
16rps 72rps 16rps 90rps 16rps 29rps
(Table8 : Compressor Operation Frequency Range)
2. OPEARTION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in the Figure9.
(Fig.9 : Compressor Control at Start-up)
01-08
30rps
60sec
47rps
60rps
120sec 180sec