The maximum value of the indoor fan speed is set as shown in Figure5, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.5 : Cool Air Prevention Control)
01-05
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure4.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow
of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table4.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -3°F
(-1.5°C)
=
-5°F > TR-Ts
(-2.5°C)
-3°F > TR-Ts > -5°F
(-1.5°C) (-2.5°C)
=
TR-Ts > -2°F
(-1°C)
=
-4°F > TR-Ts
(-2°C)
-2°F > TR-Ts > -4°F
(-1°C) (-2°C)
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
LOW mode
MED mode
MED+ mode
107.6°F (42°C)
86°F (30°C)
93.2°F (34°C)
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
Hi
Me+
Lo
Cool air
prevention
102.2°F (39°C)
98.6°F (37°C)
98.6°F (37°C)
89.6°F (32°C)
82.4°F (28°C)
S-Lo