EasyManuals Logo

Fujitsu AOU36RLX Service Instruction

Fujitsu AOU36RLX
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
SERVICE PARTS INFORMATION 3
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Check Point 2 : Check the Output DC voltage (between P and N1)
Terminal
Resistance value
L2L1
P
N2
N1
Power factor control
D1
(+)
( )
Io
L2
L1
L1,L2
P
P
Control Box
N1
N1
(+)
(+)
( )
( )
Tester(+) Tester(-)
Check the open or short-circuit
Check the Output DC voltage (between P and N1) of compressor stopping and operating.
Terminal
Resistance value
L2
P
P
N2
L2
L2
Tester(+) Tester(-)
Check the diode
If it is abnormal,replace ACTIVE FILTER MODULE
360k
0
360k
720k
5.4M (approx.)
5.3M (approx.)
5.8M (approx.)
5.4M (approx.)
Active Filter Module
Remove connector, check the open or short-circuit and the diode in the module
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping,
Active Filter Module is detective. >> Replace Active Filter Module
02-31

Other manuals for Fujitsu AOU36RLX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU36RLX and is the answer not in the manual?

Fujitsu AOU36RLX Specifications

General IconGeneral
BrandFujitsu
ModelAOU36RLX
CategoryAir Conditioner
LanguageEnglish

Related product manuals