Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check ambient temp. around motor
OK
OK
Indicate or Display:
Refer to error code table.
Outdoor Unit Fan Motor Error
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
1. Fan rotation failure 2. Motor protection by surrounding temperature rise 3. Main PCB failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
Check Point 3 : Check Output Voltage of Main PCB
Check outdoor unit circuit diagram and the voltage.
(Measure at Main PCB side connector)
If the voltage is not correct, replace Main PCB.
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is repeated
3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row, compressor and fan motor stops
permanently.
CN802
1
2
3
4
5
6
RED
BLACK
WHITE
YELLOW
BLUE
FAN MOTOR
FM
Read wire DC voltage
Red - Black
White - Black
150 380V
15 1.5V
02-25

Other manuals for Fujitsu AOU36RML1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOU36RML1 and is the answer not in the manual?

Fujitsu AOU36RML1 Specifications

General IconGeneral
BrandFujitsu
ModelAOU36RML1
CategoryAir Conditioner
LanguageEnglish

Related product manuals