En-13
36
Outdoor tempera-
ture zone bound-
ary temperature
A (*1)
-4.0°F (-20°C)
36
00
z
-0.4°F (-18°C) 0 1
3.2°F (-16°C) 0 2
6.8°F (-14°C) 0 3
10.4°F (-12°C) 0 4
14.0°F (-10°C) 0 5
17.6°F (-8°C) 0 6
21.2°F (-6°C) 0 7
24.8°F (-4°C) 0 8
For more details on settings for this item, see the Design & Technical manual.
37
Outdoor tempera-
ture zone bound-
ary temperature
B (*1)
42.8°F (6°C)
37
00
z
14.0°F (-10°C) 0 1
17.6°F (-8°C) 0 2
21.2°F (-6°C) 0 3
24.8°F (-4°C) 0 4
28.4°F (-2°C) 0 5
32.0°F (0°C) 0 6
35.6°F (2°C) 0 7
39.2°F (4°C) 0 8
42.8°F (6°C) 0 9
46.4°F (8°C) 1 0
50.0°F (10°C) 1 1
53.6°F (12°C) 1 2
57.2°F (14°C) 1 3
60.8°F (16°C) 1 4
64.4°F (18°C) 1 5
For more details on settings for this item, see the Design & Technical manual.
40
Capacity prior-
ity setting (in low
noise mode) (*1)
Off (quiet priority)
40
00
z
On (capacity priority)
01
If the cooling/heating performance becomes insufficient when the low noise mode is set, it is
possible to set “capacity priority” that automatically cancels the low noise mode (once perfor-
mance is restored, the mode will automatically return to the low noise mode).
41
Low noise mode
setting (*1)
Off (Normal)
41
00
z
On (Low noise mode)
01
42
Prohibited (Factory default)
42
00
z
55
Maximum circuit
breaker setting
Normal mode
55
00
z
20 A 0 1
30 A 0 2
For more details on settings for this item, see the Design & Technical manual.
60
Prohibited (Factory default)
60
00
z
61
Prohibited (Factory default)
61
00
z
62
Prohibited (Factory default)
62
00
z
70
Electricity meter
No. setting 1 (*2)
Setting number (x00)
70
00
z
Setting number (x01) 0 1
⁞⁞⁞
Setting number (x98) 9 8
Setting number (x99) 9 9
Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.
71
Electricity meter
No. setting 2 (*2)
Setting number (0xx)
71
00
z
Setting number (1xx)
01
Setting number (2xx)
02
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting
1 (*3)
Setting number (xx00)
72
00
z
Setting number (xx01)
01
⁞⁞⁞
Setting number (xx98)
98
Setting number (xx99)
99
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
73
Electricity meter
pulse setting
2 (*3)
Setting number (00xx)
73
00
z
Setting number (01xx)
01
⁞⁞⁞
Setting number (98xx)
98
Setting number (99xx)
99
Set the hundreds digit and thousands digit of the electricity meter pulse setting con-
nected to CN135.
90
Prohibited (Factory default)
90
00
z
92 Prohibited (Factory default) 9200
z
96 Prohibited (Factory default) 9600
z
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to CN135
become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp lights up.
(ERROR lamp is off.)
• When system is abnormal
Check the settings as there is an error in the
settings for outdoor unit address
(DIP switch SET 3-1, 2) or number of con-
nected slave units (DIP switch SET 3-3, 4).
POWER
LED105 LED104
ERROR
MODE
LED101
(GREEN)
MODE
/EXIT
SELECT EN TER
SW107
SW108 SW109
LED102
(RED)
POWER/MODE
lamp: ON
ERROR
lamp: OFF
SELECT button
ENTER
button
MODE/EXIT
button
7-segment
display:
turn off
POWER
LED105 LED104
ERROR
MODE
LED101
(GREEN)
MODE
/EXIT
SELECT EN TER
SW107 SW10 8 SW109
LED102
(RED)
POWER/MODE
lamp: ON
7-segment
display:
“-” display
ERROR lamp:
Blinking
(2) Setting method
Use the “MODE/EXIT”, “SELECT”,
and “ENTER” buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
: Press the “MODE/EXIT” button
: Press the “SELECT” button
: Press the “ENTER” button.
: Press the “ENTER” button for
more than 3 seconds.
1: Function setting
7-segment LED display (LED 105, LED 104)
(Blinking)
First 2 digits
Last 2 digits
(When [F3] to [F9] are displayed, continue to press
the “SELECT” button until [F2] is displayed.)
2: Setting the first
2 digits
3: Setting the last 2 digits
Continue to press the “SELECT” button until the
desired number appears at the last 2 digits.
Every press of the
“SELECT” button will
change the setting
number for the first 2
digits.
(Continue to press the “SE-
LECT” button until the desired
number appears at the last 2
digits.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
EXIT: Press the “MODE/EXIT” button to cancel the setting mode.