04-13
5. HEATING OPERATION
Switch airflow [AUTO], and an indoor fan motor will run
according to room temperature as below.
Airflow changeover ( Heating : Auto )
TR-Ts > -3°F
(-1.5°C)
=
-5°F > TR-Ts
(-2.5°C)
-3°F > TR-Ts > -5°F
(-1.5°C) (-2.5°C)
=
TR-Ts > -2°F
(-1°C)
=
-4°F > TR-Ts
(-2°C)
-2°F > TR-Ts > -4°F
(-1°C) (-2°C)
=
When room temperature rises
When room temperature falls
TR : Room temperature
Ts : Set temperature
Low
Me
High
6. COOL AIR PREVENTION CONTROL (Heating mode)
The maximum value of the indoor fan speed is set as shown in Fig.7, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
*On the Quiet mode,
the Quiet mode is kept
*On the Quiet mode,
the Quiet mode is kept.
.
13 min. later
SETTING
FAN MODE
Lo mode*
S-Lo
98.6°F
(37°C)
84.2°F
(29°C)
98.6°F
(37°C)
84.2°F
(29°C)
I Indoor heat exchanger
t temperature
SETTING
FAN MODE
Lo mode*
Lo mode*
ndoor heat exchanger
emperature

Table of Contents

Other manuals for Fujitsu AOUG48LMAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG48LMAS1 and is the answer not in the manual?

Fujitsu AOUG48LMAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG48LMAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals