10) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number Setting value Setting description Factory setting
60
00 Operation status
09 Error status
10 Indoor unit fan operation status
11 External heater
11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to “External heater output” in Chapter 4-4. "Details of function" on page 05-28.
Function
number
Setting value Setting description
Factory
setting
61
00 Auxiliary heater control 1
01 Auxiliary heater control 2
02 Heat pump prohibition control
03 Auxiliary heater control by outdoor temperature 1
04 Auxiliary heater control by outdoor temperature 2
05 Auxiliary heater control by outdoor temperature 3
06 Auxiliary heat pump control
07 Auxiliary heat pump control by outdoor temperature 1
08 Auxiliary heat pump control by outdoor temperature 2
09 Auxiliary heat pump control by outdoor temperature 3
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to “External heater output” in Chapter 4-4. "Details of function" on page 05-28.
Function
number
Setting
value
Setting description
Factory
setting
Setting value of function 61:
00 01 to 09
Heater: On Heater: Off Heater: On Heater: Off
62
00 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C) 0.9 °F (0.5 °C)
01 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -1.8 °F (-1 °C) 0.9 °F (0.5 °C)
02 -3.6 °F (-2 °C) -1.8 °F (-1 °C) -3.6 °F (-2 °C) 0.9 °F (0.5 °C)
03 -5.4 °F (-3 °C) -1.8 °F (-1 °C) -5.4 °F (-3 °C) 0.9 °F (0.5 °C)
04 -7.2 °F (-4 °C) -1.8 °F (-1 °C) -7.2 °F (-4 °C) 0.9 °F (0.5 °C)
05 -9.0 °F (-5 °C) -1.8 °F (-1 °C) -9.0 °F (-5 °C) 0.9 °F (0.5 °C)
06 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C) 0 °F (0 °C)
07 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -1.8 °F (-1 °C) 0 °F (0 °C)
08 -3.6 °F (-2 °C) -0.9 °F (-0.5 °C) -3.6 °F (-2 °C) 0 °F (0 °C)
09 -5.4 °F (-3 °C) -0.9 °F (-0.5 °C) -5.4 °F (-3 °C) 0 °F (0 °C)
10 -7.2 °F (-4 °C) -0.9 °F (-0.5 °C) -7.2 °F (-4 °C) 0 °F (0 °C)
11 -9.0 °F (-5 °C) -0.9 °F (-0.5 °C) -9.0 °F (-5 °C) 0 °F (0 °C)
12 -5.4 °F (-3 °C) 0 °F (0 °C) -0.9 °F (-0.5 °C) -0.9 °F (-0.5 °C)
13 -3.6 °F (-2 °C) 0 °F (0 °C) -1.8 °F (-1 °C) -0.9 °F (-0.5 °C)
14 -3.6 °F (-2 °C) 0 °F (0 °C) -3.6 °F (-2 °C) -0.9 °F (-0.5 °C)
15 -5.4 °F (-3 °C) 0 °F (0 °C) -5.4 °F (-3 °C) -0.9 °F (-0.5 °C)
16 -7.2 °F (-4 °C) 0 °F (0 °C) -7.2 °F (-4 °C) -0.9 °F (-0.5 °C)
17 -9.0 °F (-5 °C) 0 °F (0 °C) -9.0 °F (-5 °C) -0.9 °F (-0.5 °C)
1-2. Function settings by using remote controller - (05-6) - 1. Function settings (For indoor unit)
FIELD
WORKING
FIELD
WORKING

Table of Contents

Other manuals for Fujitsu AOUG48LMAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG48LMAS1 and is the answer not in the manual?

Fujitsu AOUG48LMAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG48LMAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals