Troubleshooting 4
External communication error
03-09
Detective actuators:
Detective details:
Forecast of cause :
OKOK
External communication error
Check any loose or removed connection of between the controller PCB to the external I/OPCB
>>If there is an abnormal condition, correct it by refer to installation manual or
the technical manual.
Check the connection condtion on the external I/O PCB and the controller PCB
(If there is loose connector, open cable or mis-wiring)
the same signal has not been received
for 15 seconds
After receiving signal from external I/O PCB,
1. Connection failure
2. External I/O PCB failure
3. Controller PCB failure
Check Point 1 : Check connection
Indicate or Display:
Indoor unit
Operation lamp: 1 times Flash,
Timer lamp : 8 times Flash
Wired remote control
Error code : [E : 18]
Outdoor unit (AOUG36/48LMAS1)
Check Point 2: Replace external I/O PCB
If Check Point 1 do not improve the symptom, change external I/O PCB.
OKOK
Check Point 3: Replace controller PCB
If Check Point 2 do not improve the symptom, change Controller PCB.
n
: n times blinking
: Light ON: Light OFF
Mode Error
2 5
A B FEDC
15

Table of Contents

Other manuals for Fujitsu AOUG48LMAS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOUG48LMAS1 and is the answer not in the manual?

Fujitsu AOUG48LMAS1 Specifications

General IconGeneral
BrandFujitsu
ModelAOUG48LMAS1
CategoryAir Conditioner
LanguageEnglish

Related product manuals