EasyManua.ls Logo

Fujitsu AOUH12LMAH1 - External Input and Output; External Input

Fujitsu AOUH12LMAH1
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8. External input and output
Rotary switchSW302
CN308
SW301
External input and output PCB
Indoor unit PCB
CN314
CN313
CN312
CN311
CN310
CN65
(Ext. in/out PCB)
CN47 (Ext. out)
CN46 (Ext. in)
PCB External input External output Connector Input select
Input
signal
Indoor unit
Operation/Stop
- CN46 Dry contact Edge
Forced stop
-
Operation status
CN47 - -
Error status
Indoor unit fan
operation status
Cooling thermostat
On
Heating thermostat
On
External heater
output
External input
and output (UTY-
XCSXZ2)
Operation/Stop
-
CN313/
CN314
Dry contact/
Apply voltage
Edge/Pulse
Forced stop
Forced thermostat off CN313 Edge
-
Operation status
CN310/
CN311/
CN312
- -
Error status
Indoor unit fan
operation status
External heater
output
Remote controller
output
Cooling high/low
output
Heating thermostat
On
8-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
The wire connection should be separate from the power cable line.
- 15 -
8-1. External input 8. External input and output
WALL MOUNTED
ASUG09-12LMAS
WALL MOUNTED
ASUG09-12LMAS