7. Additional charge calculation
7-1. Models: AOUH30LPAS1 and AOUH36LPAS1
Refrigerant type R410A
Factory charge amount
lb oz 4 lb 10 oz
g 2,100
¢ Refrigerant charge
Total pipe length
ft 65 or less 99 131 165 (Max.)
0.43 oz/ft
(40 g/m)
m 20 or less 30 40 50 (Max.)
Additional charge
lb oz 0 14 oz 1 lb 12 oz 2 lb 10 oz
g 0 400 800 1,200
- 71 -
7-1. Models: AOUH30LPAS1 and AOUH36LPAS1
7. Additional charge calculation
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1

Table of Contents