Installation and operating manual “1350-EN” 39
Heat pump, Split, single service
1014 U Frost-free ambient temperature setpoint from 4°C… to reduced
temperature
0,5 °C C
1016 S Maximum comfort setpoint 20…35 °C 1 °C 28 °C
1020 I Heating curve slope 0.1... 4 0,02 0.5
1021 I Off-set of the heating curve -4.50 °C… 4.5 °C 0,5 °C C
1026 S Adaptation of the heating curve (see § 3.3.2) off, ON off
1030 I Summer/Winter heating limits 8 °C 30 °C 0,5 °C 18 °C
When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the
heating (as an economy measure).
During summer mode, the display shows "Eco".
This function is only active in automatic mode.
1032 S Limit of daily heating -10 °C 10 °C 1 °C -3 °C
This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
1050 I Influence of the ambient temperature 1%... 100% 1% 20%
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1090 S Maximum optimisation on switch-on 0 360 min 10 min 120 min
1091 S Maximum optimisation on switch-off 0 360 min 10 min 120 min
1100 S Start of increase in reduced functioning mode - 30 10 °C, --- °C 1 °C ---
1101 S End of increase in reduced functioning mode - 30 10 °C, --- °C 1 °C -5°C
1130 S Mixer valve increase 0 50 °C 1 °C C
1132 S Type of servomotor 2-pos, 3-pos 3-pos
1133 S Switching differential 2-pos 0 20 °C 0,5 °C C
1134 S Servomotor travel time 30 873 s 1 s 240 s
1150 I Floor controlled drying (fig. 44) off
off: Early interruption of the current programme, programme inactive
Operational heating
Heating ready for occupation
Operational heating + ready heating
Ready heating + operational heating
Manual
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
1151 I Manual floor drying setpoint
(if line 850 = manual)
0 °C… 95°C 1 °C 25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The
concrete slab-drying programme stops automatically after running for 25 days.
1156 I Current drying day 0 ... 32
1157 I Terminated drying days 0 ... 32
1161 S Excess heat evacuation off, Heating regime,
Permanent
Permanent
Line
Function Setting range
or display
Setting
increment
Basic
setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOY54LJBYL and is the answer not in the manual?

Fujitsu AOY54LJBYL Specifications

General IconGeneral
BrandFujitsu
ModelAOY54LJBYL
CategoryHeat Pump
LanguageEnglish

Related product manuals