44 Installation and operating manual “1350-EN”
Heat pump, Split, single service
8058 I History 5 Time, Date, State code
8060 I History 6 Time, Date, State code
8062 I History 7 Time, Date, State code
8064 I History 8 Time, Date, State code
8066 I History 9 Time, Date, State code
8068 I History 10 Time, Date, State code
Generator diagnosis
8402 I Electrical resistance flow 1 Off, ON Off
8403 I Electrical resistance flow 2 Off, ON Off
8406 I Condenser pump Off, ON Off
8410 U Heat pump return temperature 0 … 140 °C
Setpoint (flow) HP 0 … 140 °C
8412 U Heat pump flow temperature 0 … 140 °C
Setpoint (flow) HP 0 … 140 °C
8413 U Compressor modulation 0 … 100%
8425 I Condenser temperature difference -50 … 140 °C
8440 I Min forced stop, compressor 1 0 … 255 min
8454 S Locking time Heat Pump
Reset ? (no, yes)
0 … 2730 h
8455 S Heat pump stops counter
Reset ? (no, yes)
0 … 65535
8456 S Hours run electrical flow
Reset ? (no, yes)
0 … 2730 h
8457 S Start counter electrical flow
Reset ? (no, yes)
0 … 65535
Diagnostics consumers
8700 U Outside temperature -50 .. 50 °C
8701 U Minimum outside temperature
Reset ? (no, yes)
-50 .. 50 °C
8702 U Maximum outside temperature
Reset ? (no, yes)
-50 .. 50 °C
8703 I Attenuated outside temperature
Reset ? (no, yes)
-50 .. 50 °C
This is the average of the outside temperature over a 24-hour period. This value is used for automatic Summer /
Winter switchover (line 730)
8704 I Mixed outside temperature -50 .. 50 °C
The mixed outside temperature is a combination of the current outside temperature and the average outside
temperature calculated by the regulator. This value is used for calculating the initial temperature.
8720 I Ambient relative humidity 0 … 100 %
8721 U Room temperature 0 .. 50 °C
8722 I Dew point 1 0 … 50 °C
8730 I Circulation pump, circuit 1 Off, ON Off
8731 I Mixer valve HC1 open Off, ON Off
8732 I Mixer valve HC1 closed Off, ON Off
Line
Function Setting range
or display
Setting
increment