The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected
temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
01-05
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.5 : Airflow change - over ( Heating : Auto ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Lo mode
Me mode
Me+ mode
42°C
30°C
34°C
When the Indoor heat
exchanger temp. rises
When the Indoor heat
exchanger temp. drops
When the Indoor heat
exchanger temp. rises
When the Indoor heat
exchanger temp. drops
* Hi or setting
Fan mode
* Me+ or setting
Fan mode
* Lo or setting
Fan mode
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 7)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(sec)
( Table 7 : Indoor fan speed )
X zone J zone
700rpm 600rpm
700rpm
Dry
Cooling
42°C
30°C
34°C
Powerful
Hi
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
<Normal operation>
<Powerful operation>
* Lower speed is selected.
* Lower speed is selected.
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.7.
It depends on the Function setting "Indoor unit fan control for energy saving."
8. INDOOR UNIT FAN CONTROL FOR ENERGY SAVING (Cooling mode)