2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the esti-
mated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number Setting value Setting description Factory setting
11
00 Standard (400 hours)
01 Long interval (1,000 hours)
02 Short interval (200 hours)
03 No indication
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac-
turer’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C
DESIGN & TECHNICAL MANUAL
- 32 -
WALL MOUNTED
ASYG07-14KMTA

Table of Contents

Other manuals for Fujitsu AOYG12KMTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG12KMTA and is the answer not in the manual?

Fujitsu AOYG12KMTA Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-splitNo
Product colorWhite
Gas hose diameter9.5 mm
Hose length (max)15 m
Inverter technologyYes
Liquid hose diameter6.35 mm
Refrigerating mediumR32
Air conditioner functionsCooling, Heating
Refrigerating medium weight700 g
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
Seasonal efficiency rating (cooling) (SEER)-
AC input voltage230 V
Current (cooling)6.5 A
Current (heating)9 A
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit noise level (high speed)- dB
Outdoor unit depth290 mm
Outdoor unit width663 mm
Outdoor unit height541 mm
Outdoor unit weight25000 g
Outdoor units quantity1
Outdoor unit noise level58 dB
Cooling airflow (outdoor unit)770 m³/h
Outdoor unit sound power level50 dB

Related product manuals