EasyManuals Logo

Fujitsu AOYG12KMTA Design & Technical Manual

Fujitsu AOYG12KMTA
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
7) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number Setting value Setting description Factory setting
44
00 A
01 B
02 C
03 D
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode 1
01 (Setting prohibited)
02 Forced stop mode
03 Operation/Stop mode 2
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both
01 Wired remote controller
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable
01 Enable
02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
02: Enable or disable this function by remote controller setting.
NOTES:
As the factory setting, this setting is initially activated.
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each re-
mote controller.
DESIGN & TECHNICAL MANUAL
- 34 -
WALL MOUNTED
ASYG07-14KMTA

Table of Contents

Other manuals for Fujitsu AOYG12KMTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG12KMTA and is the answer not in the manual?

Fujitsu AOYG12KMTA Specifications

General IconGeneral
TypeAir conditioner outdoor unit
Multi-splitNo
Product colorWhite
Gas hose diameter9.5 mm
Hose length (max)15 m
Inverter technologyYes
Liquid hose diameter6.35 mm
Refrigerating mediumR32
Air conditioner functionsCooling, Heating
Refrigerating medium weight700 g
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 46 °C
Operating temperature (heating) (T-T)-15 - 24 °C
Seasonal efficiency rating (cooling) (SEER)-
AC input voltage230 V
Current (cooling)6.5 A
Current (heating)9 A
AC input frequency50 Hz
Design load (cooling)- kW
Hourly energy consumption (cooling)- kWh
Indoor unit noise level (high speed)- dB
Outdoor unit depth290 mm
Outdoor unit width663 mm
Outdoor unit height541 mm
Outdoor unit weight25000 g
Outdoor units quantity1
Outdoor unit noise level58 dB
Cooling airflow (outdoor unit)770 m³/h
Outdoor unit sound power level50 dB