Model: AOYG14KMCC
Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
21°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12°C
2°C
19°C
10°C
0°C
Unit: rpm
Fan step
Cooling
Heating
Dry Cooling or dry at low outdoor temp.
Y zone Y zone Z zone F zone G zone
S-HIGH2 — 1,120 — — — —
S-HIGH1 990 1,120 — — — —
HIGH 990 1,120 — — — —
10 — 870 — — — —
9 990 870 990 990 990 990
8 920 870 920 920 300 280
7 920 870 920 920 300 280
6 920 710 920 630 300 280
5 920 660 920 460 270 250
4 810 660 810 380 240 220
3 670 500 670 380 220 200
2 570 500 570 380 220 200
1 520 500 520 380 200 200
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,120 rpm