Operation/Stop mode 2
In the case of “Edge” input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW302
46-03
Input of indoor unit CN46
Off → On
Operation
(R.C. enabled)
On → Off
Stop
(R.C. disabled)
1 Edge
External Input and
Output PCB
CN313
Off → On
Operation
(R.C. enabled)
On → Off
Stop
(R.C. disabled)
On
CN313
Off
On
Indoor unit operation
Off
Remote contoller
On OnOff
In the case of “Pulse” input
Function
setting
External Input and
Output PCB
External input Input signal Command
Rotary
switch
SW302
46-03 1 Pulse
External Input and
Output PCB
CN313
Pulse
Operation
(R.C. enabled)
CN314
Stop
(R.C. disabled)
On
On
Off
On
Off
Remote controller
On
Off
Indoor unit operation
CN313
CN314
Off
On
NOTE:
When “Operation/Stop” mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
2-4. Details of control input function