8. COMPRESSOR CONTROL
01-09
1. OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 12.
Cooling / Dry Heating
Minimum Maximum Minimum Maximum
ASYG07/ 09LECA
ASYG12/ 14LECA
22rps 79rps 23rps 99rps
96rps
18rps18rps
130rps
ASYG07/ 09LECA
70rps 82rps
92rps 96rps
ASYG12/ 14LECA
56rps 74rps
87rps
(Table 12 : Compressor frequency range)
2. OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the start-up is controlled as shown in the Fig.10
(Fig.10 : Compressor control at start-up)
Time
Time Time Time
Time
(Frequency)
Frequency
Frequency
Frequency Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
Time
Time Time Time
Time
ASYG07/ 09LECA
80sec 140sec 200sec 440sec
ASYG12/ 14LECA
80sec 140sec 200sec
(Time)
97rps
108rps
Frequency
Time
6
Frequency
Time
6
119rps
380sec
500sec440sec
3. LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table13.
Under Over Under Over Under Over
ASYG07/09LECA
ASYG12/14LECA
34rps 28rps 30rps
30rps
39rps 27rps
22rps
18rps
(Table13 : Limitation of Compressor Frequency)
10°C 14°C 40°C
Under Over Under Over Under Over Under Over
ASYG07/09LECA
ASYG12/14LECA
36rps 27rps
42rps 39rps
27rps 18rps
28rps
30rps
30rps23rps
- 3°C 7°C 14°C 40°C
[ Cooling/ Dry ]
[ Heating ]