2-15. E: 57. Damper (Open/Close) detection limit switch error
Indicator
Wired remote
controller
Error code E: 57
Detective actuator
Indoor unit main PCB When limit switch were not able to detect the close
though the damper close.(Upper air flow)
When limit switch were not able to detect the open
though the damper open.(Upper & Lower air flow)
Limit switch
Damper
Forecast of cause
Limit switch failure
Shorted connector/wire
Damper faulure
Controller PCB failure
Check point 1. Check limit switch
Check operation of limit switch. (any blocking by dust, etc.)
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
Check point 3. Check Damper
Check the obstruction of damper movement.
Check the damper movement.
-> Replace damper if the damper is abnormal
Check point 4. Replace main PCB
If Check Point 1 and 3 do not improve the symptom, change main PCB.
End
2-15. E: 57. Damper (Open/Close) detection limit switch error - (03-19) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AOYG22KBTB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG22KBTB and is the answer not in the manual?

Fujitsu AOYG22KBTB Specifications

General IconGeneral
BrandFujitsu
ModelAOYG22KBTB
CategoryAir Conditioner
LanguageEnglish

Related product manuals