3-4. Branch pipes
¢
Branch pipe selection
Twin connection Triple connection
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Connection
type
Kit name
Kit
number
Outdoor unit
Piping diameter: mm (in)
Indoor
unit
number
Kit to outdoor
unit*
Kit to indoor unit
Twin UTP-SX236A 1
AOYG36KBTB
Liquid: 9.52 (3/8)
Gas: 15.88 (5/8)
Liquid: 6.35 (1/4)
Gas: 12.70 (1/2)
2AOYG45KBTB
AOYG54KBTB
Triple UTP-SX354A 1 AOYG54KBTB
Liquid: 9.52 (3/8)
Gas: 15.88 (5/8)
Liquid: 6.35 (1/4)
Gas: 12.70 (1/2)
3
*: For the diameter of the connection piping between the outdoor unit and the branch pipes, refer to
the installation manual of the outdoor unit.
- 107 -
3-4. Branch pipes 3. Pipe installation