5. System setting
5-1. Indoor unit setting
Setting Setting range Setting method
Set A
Indoor unit
Primary/Secondary
“00” or “01”
Refer to Chapter 8-8. "Function details" on page
183. (Function number: 51)
Set B
Refrigerant circuit
address
“00” to “15”
Refer to Chapter 8-8. "Function details" on page
183. (Function number: 02)
Set C
Remote controller
address
“00” to “15”*
Refer to Chapter 8-8. "Function details" on page
183
. (DIP switch setting)
NOTES:
◌: Setting is required.
●: By a case, setting is required.
*: Set the remote controller address in the order of “00”, “01”, “02”,..., “15”. (Blank is not al-
lowed).
¢
Twin type
Connection example 1
Refrigerant pipe
Connection cable
Remote controller cable
SetASetB SetC
(00)
(00)(00)
SetASetB SetC
0
1 01
(00)
<Twin>
Indoor unit
Outdoor unit
Wired remote controller
Junction box
Connection example 2
Refrigerant pipe
Connection cable
Remote controller cable
SetASetB SetC
(00)
0
1 02
SetASetB SetC
0
1 01 03
SetASetB SetC
(00)
(00)(00)
SetASetB SetC
0
1 01
(00)
<Twin> <Twin>
Indoor unit
Outdoor unit
Wired remote controller
Junction box
NOTE: (00) is factory setting.
- 126 -
5-1. Indoor unit setting 5. System setting
SYSTEM
DESIGN
SYSTEM
DESIGN

Table of Contents

Other manuals for Fujitsu AOYG36KBTB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG36KBTB and is the answer not in the manual?

Fujitsu AOYG36KBTB Specifications

General IconGeneral
BrandFujitsu
ModelAOYG36KBTB
CategoryAir Conditioner
LanguageEnglish

Related product manuals