Loading...
- 28 -
WALL MOUNTED
ASYG30, 36LMTA
External input and output PCB
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
Output voltage: High DC 12 V±2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to Chapter 10-3. "Combination of external input and output" on page 29.
When indicator or other components are connected directly
Example: Function setting 60 is set to "00".
When connecting with a device equipped with a power supply
Example: Function setting 60 is set to "00".
1
2
Connector
(CN310)
LED 1
(Operation status)
PCB
Resistor
Connected unit
+
-
1
2
Connector
(CN311)
LED 2
(Error status)
Resistor
+
-
1
2
Connector
(CN312)
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
1
2
Connected device 1
Connector
(CN310)
PCBConnected unit Relay
(Operation status)
-
+
1
2
Connected device 2
Connector
(CN311)
(Error status)
-
+
1
2
Connected device 3
Connector
(CN312)
(Indoor unit fan
operation status)
-
+