EasyManua.ls Logo

Fujitsu AOYG36LMTA - Additional Charge Calculation; Model: AOYG30 LMTA; Model: AOYG36 LMTA

Fujitsu AOYG36LMTA
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 58 -
OUTDOOR UNIT
AOYG30, 36LMTA
6. Additional charge calculation
6-1. Model: AOYG30LMTA
Refrigerant charge
6-2. Model: AOYG36LMTA
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200
Refrigerant type R410A
Refrigerant amount g 2,100
Total pipe length m 20 or less 30 40 50 (Max.)
40 g/m
Additional charge g 0 400 800 1,200

Related product manuals