WALL MOUNTED
ASYG30, 36LMTA
Supporting operation
When the room temperature does not reach to the set point after a certain period of time, regard-
less of the primary-secondary relation of the unit, operation start indication is issued to another
unit and both indoor units perform air conditioning simultaneously.
NOTE: While performing this function, following functions cannot be used:
Operation modes other than cooling
Airflow modes other than HIGH
Temperature setting other than 24 °C
POWERFUL mode
10 °C HEAT operation
ECONOMY operation
On/off timer, program timer, and SLEEP timer
Weekly timer on secondary unit
Human sensor function
Shutdown operation
Starting operation on secondary unit
To stop the operation, shutdown the power supply.
On
Indoor unit A
Indoor unit B
Off
On
Off
Set point non-attainment
*: Operaion is started even when the unit is stopped by the weekly timer.
Ts + 0.5 °C
Ts + 2.5 °C
Supporting operation: On
Supporting operation: Off