EasyManua.ls Logo

Fujitsu AOYG45LBTA - Page 77

Fujitsu AOYG45LBTA
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 71 -
DUCT TYPE
ARYG12-54LHTBP
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function no. Functions
1)
11
Filter sign
2)
26
Static pressure
3)
30/31
Room temperature control for indoor unit sensor
4)
35/36
Room temperature control for wired remote controller sensor
5)
40
Auto restart
6)
42
Room temperature sensor switching
7)
43
Cold air prevention
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
11)
49
Indoor unit fan control for energy saving for cooling
12)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours)
01 Long interval (4,400 hours)
02 Short interval (1,250 hours)
03 No indication