08-08
OUTDOOR UNIT
PROTECTION FORM AO*18LMAKL AO*24LMAKL
FUSE (SIDE OF POWER SUPPLY TERMINAL) -
FUSE (SIDE OF INDOOR UNIT) -
-
-
FAN MOTOR PROTECTOR THERMAL PROTECTOR
FUSE ON MAIN PCB
8-4. SAFETY DEVICE
THERMAL SWITCH
PRESSURE SWITCH
25A 250V
150°C ± 5°C OFF
OFF 120 ± 5°C
ON 85 ± 7°C
COMPRESSOR
5.0A 250V
4.2MPa OFF
3.15A 250V
MODEL NAME PROTECTION FORM AO*30LMAWL AO*36LMAWL
- 25A 250V 25A 250V
- 10A 250V 10A 250V
- 3.15A 250V 3.15A 250V
- 5A 250V 5A 250V
FUSE ON POWER PCB - - -
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C ± 5°C OFF 150°C ± 5°C OFF
COMPRESSOR - - -
HIGH PRESSURE PROTECTION
-
OFF:4.2 ± 0.1MPa
ON:3.2 ± 0.15MPa
OFF:4.2 ± 0.1MPa
ON:3.2 ± 0.15MPa
LOW PRESSURE PROTECTION - - -
TERMINAL FUSE - - -
DISCHARGE THERMOSTAT
-
OFF:120 ± 5°C
ON:80 ± 15°C
OFF:120 ± 5°C
ON:80 ± 16°C
COMPRESSOR THERMOSTAT
-
OFF:130 ± 5°C
ON:80 ± 16°C
OFF:130 ± 5°C
ON:80 ± 17°C
FUSE (SIDE OF POWER SUPPLY TERMINAL)
FUSE ON MAIN PCB
MODEL NAME PROTECTION FORM
AO 45LJAYL
AO 45LJBYL
AO 54LJAYL
FUSE (SIDE OF INDOOR UNIT) - 10A 250V 10A 250V
- 3.15A 250V 3.15A 250V
- 5A 250V 5A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C ± 5°C OFF 150°C ± 5°C OFF
COMPRESSOR - 165°C±5°C OFF 165°C ± 5°C OFF
HIGH PRESSURE PROTECTION - DC5V 4.2MPa DC5V 4.2MPa
FUSE ON MAIN PCB