08-14
DIP SWITCH SETTING
1-1 Low static pressure function setting
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
2-1 Room temperature correct coefficient of heating.
R
O
T
A
R
Y
S
W
I
T
C
H
S
E
T
T
I
N
G
In case of installing in low static , you can minimize air flow and noise.
Decide the heating temperature correct coefficient vale of heating.
2-2 External input select edge/pulse
( Factory setting)
SW1-1 SW state
OFF Normal
ON Low static pressure
( Factory setting)
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
HEAT TEMPERATURE CORRECTION
( Factory setting)
SW2-1 SW state
OFF +4 deg (Ceiling setting)
ON 0 deg (Room setting)
( Factory setting)
SW2-2 SW state
OFF Edge
ON Pulse
AUTORESTART SETTING
( Factory setting)
SW2-3 SW state
OFF Validity
ON Invalidity
( Factory setting)
SW3 SW state
0 single
1-15 Indoor unit address
This switch is used to select the format of external input command as
shown in the table below.
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
This switch can be used when group control system.
Set the indoor unit address in the 1,2,-,15 order.