EasyManua.ls Logo

Fujitsu AR 18LUAD Series - Page 43

Fujitsu AR 18LUAD Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Defrost Flow Chart
3-1. For AR*18LUAD/ 24LUAN
The defrosting shall proceed by the integrating operation time as follows.
(Not defrosted for 6 or 10 minutes)
3 sec later Compressor OFF
3 sec later Outdoor fan motor OFF
28 sec later 4-way valve OFF
34 sec later compressor ON
(Frequency : 95 Hz)
Heating operation start : Compressor ON
Defrost Indicator:
[Operation lamp]
9 sec ON / 1 sec OFF
Outdoor heat exchanger temperature: Over 10°C
or
Compressor ON time: Over 15 minutes
Defrost end
05-15
Compressor integrating operation: 40 minutes and over
Outdoor heat exchanger temperarure: Below -8°C
Defrost start

Related product manuals