4. OUTDOOR FAN CONTROL
Following table shows the fan speed of the outdoor unit.
1. Outdoor Fan Motor
*
For AO*18LMAK2/ 24LMAM2
When the outdoor heat exchanger tenperature is lower than 2°C,
the fan speed switches to 780rpm on heating mode.
For AO*30LMAW4
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger tenperature is lower than 2°C,
the fan speed switches to 780rpm on heating mode.
*
( Table 3 : Fan speed of the outdoor unit )
780/ 420 rpm
820/ 780/ 400/ 300/ 200 rpm
850/ 780/ 400/ 300/ 200 rpm
780/ 420 rpm
Cooling
Heating
AO*18LMAK2
AO*30LMAW4
AO*24LMAM2