EasyManuals Logo
Home>Fujitsu>Air Conditioner>ARXG22KMLA

Fujitsu ARXG22KMLA User Manual

Fujitsu ARXG22KMLA
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
2-26. E: 94. Trip detection (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 94
Detective actuator Outdoor unit
Inverter PCB Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE: The number of generations is reset when the
compressor starts up.
Main PCB
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Inverter PCB
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check point 2. Replace inverter PCB
If Check point 1 do not improve the symptom, change inverter PCB.
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
End
2-26. E: 94. Trip detection (Outdoor unit) - (03-30) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ARXG22KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG22KMLA and is the answer not in the manual?

Fujitsu ARXG22KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG22KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals