1. Specifications
Type
Duct
Inverter heat pump
Model name ARXG24KHTAP ARXG30KHTAP
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Capacity
Cooling
Rated
kW 6.8 8.5
Btu/h 23,200 29,000
Min.—Max.
kW 0.9—8.0 2.8—10.0
Btu/h 3,100—27,300 9,600—34,100
Heating
Rated
kW 7.5 10.0
Btu/h 25,600 34,100
Min.—Max.
kW 0.9—9.1 2.7—11.2
Btu/h 3,100—31,000 9,200—38,200
Input power
Cooling
Rated
kW
1.89 2.65
Max. 2.94 3.83
Heating
Rated 1.85 2.63
Max. 2.57 4.37
Fan
HIGH
W
70 150
MED 40 100
LOW 25 75
QUIET 15 65
Current
Cooling
Rated A
8.3 11.7
Heating 8.1 11.7
Power factor
Cooling
%
98.7 98.1
Heating 98.7 97.7
EER Cooling
kW/kW
3.60 3.21
COP Heating 4.06 3.80
Moisture removal L/h (pints/h) 1.8 (3.2) 2.3 (4.0)
Maximum operating current *1
Cooling
A
13.6 22.6
Heating 13.6 22.6
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,360 1,700
MED 1,080 1,360
LOW 880 1,190
QUIET 680 1,070
Heating
HIGH 1,360 1,700
MED 1,080 1,360
LOW 880 1,190
QUIET 680 1,070
Type × Q'ty Sirocco fan × 2
Motor output W 197 375
Static pressure range Pa 30 to 200
Sound pressure level *2
Cooling
HIGH
dB (A)
32 36
MED 28 33
LOW 24 30
QUIET 21 29
Heating
HIGH 32 36
MED 28 33
LOW 24 30
QUIET 21 29
Sound power level
Cooling
dB (A)
57 63
Heating 57 65
Heat exchanger type
Dimensions (H × W × D)
mm
420 × 758 × 39.9
Fin pitch 1.4
Rows × Stages 3 × 20
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color ―
Dimensions
(H × W × D)
Net
mm
300 × 1,000 × 700
Gross 400 × 1,238 × 875
Weight
Net
kg
36
Gross 43 44
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (1/4) Ø 9.52 (3/8)
Gas Ø 12.70 (1/2) Ø 15.88 (5/8)
Method Flare
Drain hose
Material PVC
Size mm Ø 25 (I.D.), Ø 32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Remote control (Option)
Wired remote controller, Wireless remote controller, Mobile app*3 (FGLair
™
)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
– Standard static pressure; 24 type: 35 Pa, 30 type: 47 Pa
• Protective function might work when using it outside the operation range.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.