¢ Heat exchanger temperature thermistor
Temperature (°C) Resistance (kΩ) Voltage (V)
-30.0 95.58 0.24
-25.0 68.90 0.32
-20.0 50.31 0.43
-15.0 37.19 0.57
-10.0 27.81 0.73
-5.0 21.02 0.92
0.0 16.05 1.14
5.0 12.38 1.39
10.0 9.63 1.65
15.0 7.56 1.93
20.0 5.98 2.21
25.0 4.77 2.49
30.0 3.84 2.77
35.0 3.11 3.02
40.0 2.53 3.26
45.0 2.08 3.48
50.0 1.71 3.68
55.0 1.42 3.85
60.0 1.19 4.00
65.0 1.00 4.13
70.0 0.84 4.25
75.0 0.71 4.35
80.0 0.61 4.43
¢ Outdoor temperature thermistor
Temperature (°C) Resistance (kΩ) Voltage (V)
-30.0 224.33 0.73
-25.0 159.71 0.97
-20.0 115.24 1.25
-15.0 84.21 1.56
-10.0 62.28 1.90
-5.0 46.58 2.26
0.0 35.21 2.61
5.0 26.88 2.94
10.0 20.72 3.25
15.0 16.12 3.52
20.0 12.64 3.76
25.0 10.00 3.97
30.0 7.97 4.14
35.0 6.40 4.28
40.0 5.18 4.41
45.0 4.21 4.51
50.0 3.45 4.59
55.0 2.85 4.65
5-2. Outdoor unit - (03-70) - 5. Thermistor resistance values