3-2. Outdoor fan control
¢ Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢ Fan speed
Model: AOHG36KBTB
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step Cooling or dry Heating
13 830
12 830
11 740
10 700 830
9 650 740
8 570 690
7 570 620
6 570 590
5 570 480
4 540 410
3 480 340
2 400 270
1 270 200
S-HIGH 830
When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 830 rpm