Trouble shooting 13
OUTDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause :
OK
Indicate or Display:
Compressor Location Detection Error
Outdoor Unit Inverter PCB
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
1. Connector connection failure 2.Inverter PCB failure
Check Point 1 : Check connections condition in control unit
When "compressor location detection error" is detected consecutively
5 times, within 40 seconds after start-up.
02-15
Refer to error code table.
Check Point 2 : Replace Inverter PCB
If Check Point 1 do not improve the symptom, replace or Inverter PCB.