< AB*G / AUYG type >
42°C
30°C
34°C
When Indoor heat exchanger
temperature rises
When Indoor heat exchanger
temperature drops
Hi
*Me+ or setting
FAN mode
Cool air
prevention
39°C
37°C
37°C
32°C
24°C
S-Lo
*Lo or setting
FAN mode
< AG*G type >
*Lower speed is selected
42°C
30°C
31°C
When Indoor heat exchanger
temperature rises
When Indoor heat exchanger
temperature drops
Hi
*Me or setting
FAN mode
Cool air
prevention
39°C
37°C
34°C
29°C
24°C
S-Lo
*Lo or setting
FAN mode
*Lower speed is selected
Compressor
ON
OFF
Indoor fan
Setting air flow
OFF
Function setting 49 Note
Setting air flow
Work
In the case of 3 wire remote controller (UTY-RVN*N)
is connected, set it to 0 or 1.
This controller can’t be set it.
10
0
1
30 60 180 60 180 60 10 30
(sec)
S-Lo
480rpm
Factory setting
( Fig 8 : Indoor Fan Control)
7. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig.8.
01-11