22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVER RISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency
is decreased 30rps, and it continues to decrease thefrequency for 30rps every 120 seconds until the
temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the compressor
frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor stops.
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
AO*G36LBLA5
AO*G45LBLA6
104°C 101°C 110°C
Temperature
Temperature Temperature
( Table 18 : Discharge temperature over rise prevension control / Release temperature )
3. COOLING PRESSURE OVER RISE PROTECTION
When the outdoor unit discharge pressure sensor rises to 4 MPa or greater,
the compressor is stopped and error display is indicated.
01-35

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07LUCA Series and is the answer not in the manual?

Fujitsu AS G07LUCA Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07LUCA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals