3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
3 sec later Compressor : OFF
3 sec later Outdoor fan motor : OFF
35sec later 4WAY valve : OFF
41sec later Compressor : ON
Heating operation start : Compressor ON
Outdoor HEX temp. : Over 15°C
Compressor ON time : Maximum 15 minutes
Defrost end
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Tn < -17°C
Ta > -10°C
Tn < 0.8 ×Ta - 11.6
Tn < -24°C
=
=
Tn - Tn-1 < -2°C
and Sn = Sn-1
=
Ta < -20°C
tsorfed gnitargetnItsorfed gnitargetnItsorfed lamroN
(Integrating OFF count defrost)
-20°C < Ta < -10°C
Tn < -6°C More than 210 minutes
( For continuous operation )
or
Tn < -3°C
(and after 30 minutes,
if the Tn < -3°C
(and after 3 minutes,
if the Tn < -5°C
Tn < -5°C
or
=
=
Tn < 0.8 ×Ta - 11.6
Tn < -28°C
=
=
=
Compressor OFF count :
40 times
(Less than 10 minutes)
or or
Tn
Ta
Tn-1
Sn
Sn-1
: Outdoor heat exchanger temp.
: Outside air temp.
: Before 5 minutes detected Tn
: Number of operation indoor units
: Before 5 minutes detected Sn
01-30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AS G07LUCA Series and is the answer not in the manual?

Fujitsu AS G07LUCA Series Specifications

General IconGeneral
BrandFujitsu
ModelAS G07LUCA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals