OUTDOOR UNIT
AOTG09-22LV
OUTDOOR UNIT
AOTG09-22LV
ADDITIONAL CHARGE CALCULATION6.
MODEL
:AOTG09LV
Refrigerant charge
MODEL
:AOTG12LV
Refrigerant charge
MODEL
: AOTG18LV
Refrigerant charge
MODEL
:AOTG22LV
Refrigerant charge
Refrigerant type R410A
Refrigerant amount g 850
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1050
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1450
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100
Refrigerant type R410A
Refrigerant amount g 1550
Total pipe length m 15 or less 20 (MAX)
20g/m
Additional charge g 0 100